Water treatment
Cooling tower water treatment · FIONER
Control algae, biofilm and scale in cooling towers and evaporative condensers without dosing biocides or chemicals.
FIONER is developed by FRIMONT: a controlled ionic input keeps the circuit clean and lets you run more cycles of concentration, with less blowdown and less water.

Applications
What it solves.
In a cooling tower, evaporating water leaves its salts in the circuit, while the air brings in dust, pollen and nutrients. The result is limescale and biofilm: less heat transfer, higher power consumption and bacteria sheltered where biocide cannot reach. FIONER tackles both problems from the water circuit itself.
- Open cooling towers in industrial plants and air-conditioning systems.
- Evaporative condensers in ammonia refrigeration plants.
- Coils and heat exchangers with scale that currently requires acid cleaning.
- Circuits that need to cut water consumption and blowdown volume.
Configurations
A configuration tailored to your application.
Technical selection defines the equipment and its integration with the process.
Biological control without biocides
FIONER electrodes release ions into the water flowing through the dispenser. Wherever there is liquid water they eliminate algae, fungi and biofilm; bacteria and viruses are eliminated fully or partially depending on the selected electrode. It helps prevent Legionella without handling or storing biocides.
Scale: prevention and recovery
Carbonates and bicarbonates lose their structural strength. New scale does not form, and existing deposits slowly break down into sludge and come off, with no acid or aggressive cleaning of the equipment. The coil recovers its heat-transfer surface.
Less water, less blowdown
FIONER controls the blowdown of the tower basin and allows higher cycles of concentration: less make-up water, less continuous blowdown and less effluent.
Installation and control
The dispenser is installed in line on the recirculation pipe and a control panel regulates the treatment. There are no chemicals to replenish: only the electrode kit is replaced when the controller calls for it.
Functions
- Treatment power adjustable in 10 levels: shock or maintenance.
- Automatic blowdown of the basin water.
- Worn-electrode alarm and operating history.
- Own consumption of about 200 W, depending on treatment power.
- One controller handles up to 10 FIONER units and links to the FCX system.
Technical data
Reference values.
How much capacity scale takes away
Thermal capacity of a heat exchanger by limescale thickness.
| Scale thickness | Thermal capacity | Performance |
|---|---|---|
| 0 mm | 1,019,207 kcal/h | 100% |
| 0.5 mm | 751,283 kcal/h | 74% |
| 1 mm | 593,887 kcal/h | 58% |
| 1.5 mm | 493,947 kcal/h | 48% |
| 2 mm | 420,844 kcal/h | 41% |
| 3 mm | 327,169 kcal/h | 32% |
Calculated with Q = U · S · LMTD. With 1 mm of scale, the same unit delivers 42% less.
What a higher condensing temperature costs
Screw compressor in a refrigeration plant, by condensing temperature.
| Condensing temperature | Refrigeration capacity | Absorbed power | COP |
|---|---|---|---|
| 28 °C | 685 kW | 275 kW | 2.49 |
| 30 °C | 676 kW | 286 kW | 2.36 |
| 32 °C | 666 kW | 298 kW | 2.23 |
| 35 °C | 652 kW | 316 kW | 2.06 |
| 38 °C | 637 kW | 335 kW | 1.90 |
| 40 °C | 627 kW | 348 kW | 1.80 |
| 42 °C | 616 kW | 361 kW | 1.71 |
Compressor manufacturer's selection. A condenser with scale and biofilm condenses hotter: from 28 °C to 42 °C the compressor absorbs 86 kW more and delivers 69 kW less cooling.




Selection
How we define the solution for your process.
We start from what you need to achieve and your facility conditions. We guide you through defining requirements and selecting an appropriate configuration. You do not need to have all this data to start the conversation.
What we evaluate during technical definition
- Equipment use
- FIONER pays off when the tower or condenser operates more than 3 months a year.
- Equipment to treat
- Make and model, dimensions, materials, thermal capacity, water flow and recirculation pipe diameter.
- Current condition
- Photos of the outside and inside of fills, coils and basin. FIONER is not corrosive, but it does not repair earlier damage: if scale was covering corrosion, removing it exposes the metal. That is why we document the condition before installing.
- Water and utilities
- Make-up water analysis, pH between 7 and 8, power supply, level control and a discharge point for blowdown.
Documentation
Technical documentation.
Request technical documentation for the configuration required by your process. Tell us about your application and operating conditions to guide the inquiry.
Request technical documentationEngineering and integration
Scope is defined with you.
From equipment selection to integration, installation, and commissioning, we agree on what the project needs and how it connects to your facility. Control systems and after-sales service are integral parts of that conversation.
What we can undertake